Current clamp transducer AC calibration
EPTIS ID: 882534
PT scheme / program name: Electrical calibration
PT item type: AC/DC Voltage, AC/DC Current, Resistance
Sample / item: current clamp transducer AC
Model: Hioki CT9667-02
External provider for the calibration of the PT item: an ISO/IEC 17025 accredited laboratory or NMI, used by AG Metrology (PT provider) to determine the assigned value
Measurement points:
Range 500 A (1mV AC / A) 50 Hz ⇒ (50, 450) A
Range 5000 A (0.1 mV AC / A) 50 Hz ⇒ (500, 1500, 2500, 3500, 4500) A
CMC from the calibration laboratory’s accreditation schedule:
| Range | 50 mA < I ≤ 100 A | 40 Hz ≤ f ≤ 60 Hz | 1.3 x 10^-4 x I |
|---|---|---|---|
| 100 A < I ≤ 240 A | 40 Hz ≤ f ≤ 60 Hz | 1.9 x 10^-4 x I | |
| 240 A < I ≤ 10 kA | 40 Hz ≤ f ≤ 60 Hz | 1.0 x 10^-4 x I |
The uncertainty actually used depends on the istrument and a stability contribution, finalised each round. The laboratory only calibrates; AG Metrology alone determines the assigned value and is responsible for the PT scheme.
Note: Indications regarding organizational methods, presentation and sending of results will be reported in the PT participation protocol
Scheduled start date for PT: every year in March
Payment: bank transfer